- Capacity: 5.5kW / 30A Single-Phase 208/230V (de-rated to 24A continuous)
- Outlets: 16 C13 & 2 C19 across two metered 9-outlet load banks with 20A breakers
- Metering: Dual digital meters display real-time output current per load bank
Ensure critical equipment stays powered and balanced with the Eaton Tripp Lite PDUMH30HV6, a 5.5kW single-phase local metered PDU engineered for optimal power distribution and monitoring. You can confidently power up to 18 devices using its 16 C13 and two C19 208/230V outlets, perfect for network IT applications, small computer rooms, and various equipment rack setups. The PDU's integrated digital ammeter provides real-time current metering for two separately breakered load banks, allowing you to monitor and balance loads precisely to prevent costly overloads and maintain continuous operation.
Maintaining proper load levels within your rack is simple, minimizing the risk of downtime and extending equipment lifespan. This 2U rack-mountable PDU installs effortlessly in standard 19-inch racks with included hardware, and its 1.8 meter (6 ft) cord with a NEMA L6-30P input plug ensures a secure connection to your power source. Plus, the PDUMH30HV6 is TAA-compliant, making it an ideal choice for federal procurement contracts and government GSA Schedule purchases.
View Data SheetFuture-proof your network with the Eaton Tripp Lite PDUMH30HV6, a 5.5kW single-phase local metered PDU that offers real-time current monitoring across two separately breakered load banks, preventing costly overloads and ensuring optimal load balance for your critical IT infrastructure. This 2U rack-mountable PDU boasts 16 C13 and 2 C19 outlets, a 1.8 m (6 ft) cord with a NEMA L6-30P input, and includes plug-lock sleeves to secure connections, all within a TAA-compliant package ideal for government procurement.
| Product Type: | Computing Device Accessory |
|---|---|
| PDU Type: | Local Metered, Single-Phase |
| Input Voltage: | 208/230V |
| Input Plug: | NEMA L6-30P |
| Maximum Input Current: | 24A continuous (agency de-rated) |
| Output Capacity: | 5.5kW (230V) / 5kW (208V), 30A max (de-rated to 24A) |
| Output Receptacles: | (16) C13 & (2) C19 208/230V outlets |
| Overload Protection: | Two 20A breakers, 9 outlets each |
| Frequency Compatibility: | 50/60 Hz |
| Input Cord Length: | 1.83 m (6 ft) |
| Mounting: | 2U Rack-Mount (Horizontal), EIA-Standard 19 in. rack |
| Rack Height: | 2U |
| Minimum Rack Depth: | 40.64 cm (16 in) |
| Dimensions: | 88.9 x 444 x 317.5 mm (3.5 x 17.5 x 12.5 in) |
| Weight: | 6.21 kg (13.7 lbs) |
| Material: | Metal |
| Operating Temperature: | 0° to 40°C (32° to 104°F) |
| Storage Temperature: | -30° to 50°C (-22° to 122°F) |
| Relative Humidity: | 5% to 95% non-condensing |
| Operating Elevation: | 0–3000 m (0–10,000 ft) |
| Certifications: | UL 62368-1, NOM (Mexico), RoHS, FCC Part 15 Class A, UKCA, TAA |